020-8786 2699
020-8786 2699

Water source fan coil unit 1000Ⅱ Consult immediately
Product Details

Item

Model

FL(R)FP-

1000Ⅱ

Unit Performance

Cooling Capacity

kW

11.31

Heating Capacity

kW

12.48

Airflow

m³/h

2299

Standard Type

Cooling Rated Power

kW

2.635

Heating Rated Power

kW

2.95

Cooling Rated Current

A

5.34

Heating Rated Current

A

5.98

High Static Pressure Type

Cooling Rated Power

kW

2.723

Heating Rated Power

kW

3.038

Cooling Rated Current

A

5.52

Heating Rated Current

A

6.15

Power Supply


380V,50Hz

Outdoor Unit

Refrigerant

Refrigerant Name


R410A

Charge Amount

kg

2.1

Water Heat Exchanger

Connection Size

mm

2×DN40

Circulating Water Flow Rate

m³/h

2.924

Water Side Resistance

kPa

43.6

Noise

dB(A)

39

Dimensions

Length

mm

600

Width

mm

480

Height

mm

585

Weight

kg

92

Positive Pressure Indoor Unit

Standard Type

External Static Pressure

Pa

25

Noise

dB(A)

43.7

High Static Pressure Type

External Static Pressure

Pa

40

Noise

dB(A)

44.8

Dimensions

Length

mm

1550

Width

mm

480

Height

mm

235

Weight

kg

36

Condensate Drain Connection

mm

DN20

Indoor/Outdoor Unit Connection Main Pipe

Liquid Pipe

mm

Φ9.52

Gas Pipe

mm

Φ15.88


b06d934057fedec69a99a20ded00d341
Leave an online message Leave an online message Telephone consultation Telephone consultation

020-8786 2699

WeChat consultation WeChat consultation
WeChat consultation
Back to the top Back to the top