Item Model | FL(R)FP- | 1200II-K4 | |||
U N I T | Cooling capacity | kW | 12 | ||
Heating capacity | kW | 12.98 | |||
Air flow | m³/h | 2000 | |||
Cooling rated power | kW | 2.951 | |||
Heating rated power | kW | 3.179 | |||
Cooling rated current | A | 5.6 | |||
Heating rated current | A | 6.04 | |||
Power supply | 380V3N~50Hz | ||||
O D U | Refrigerant | Type | R410A | ||
Charge amount | kg | 2.3 | |||
Water heat exchanger | Connection size | mm | 2×DN40 | ||
Circulating water flow rate | m³/h | 3.313 | |||
Water side pressure drop | kPa | 45.3 | |||
Noise | dB(A) | 40 | |||
Dimensions | Length | mm | 600 | ||
Width | mm | 480 | |||
Height | mm | 625 | |||
Weight | kg | 94 | |||
I D U | Noise | dB(A) | 50 | ||
Dimensions | Panel size | mm | 953×953×50 | ||
Chassis size | mm | 857×857×470 | |||
Weight | kg | 54 | |||
Condensate pipe size | mm | DN25 | |||
Indoor/outdoor connection pipe | Liquid pipe | mm | Φ9.52 | ||
Gas pipe | mm | Φ15.88 | |||