Item model | L(R)GD- | 140Ⅱ | ||
Unit performance | Cooling capacity | KW | 76.56 | |
Heat production | KW | 81.92 | ||
Air volume | m³/hr | 14000 | ||
Refrigeration power rating | KW | 20.62 | 22.22 | |
Rated power for heating | KW | 23.49 | 25.45 | |
Refrigeration current rating | A | 41.77 | 45.01 | |
Heating rated current | A | 47.59 | 51.56 | |
External static pressure | Pa | 125 | 450 | |
Unit noise | dB(A) | 68.5 | 70 | |
Power supply | 380V 3N~50Hz | |||
Refrigerant | Working quality | R410A | ||
Charging volume | kg | 4×2.70 | ||
Water heater | Take over the specifications | mm | 4×DN50 | |
Circulating water flow | m³/hr | 21.113 | ||
Waterside resistance | KPa | 55.0 | ||
Condensate pipe specifications | mm | 2*DN25 | ||
weight | kg | 850 | ||
Dimensions | Long | mm | 1720 | |
Wide | mm | 1700 | ||
High | mm | 980 | ||