Item model | FL(R)GD- | 40II | ||||
Unit Performance | Cooling capacity | kW | 19.24 | |||
Heat production | kW | 21.24 | ||||
Air volume | m³/hr | 4000 | ||||
Refrigeration power rating | kW | 4.79 | 4.96 | 4.97 | ||
Rated power for heating | kW | 5.33 | 5.5 | 5.51 | ||
Refrigeration current rating | A | 9.7 | 10.05 | 10.07 | ||
Heating rated current | A | 10.8 | 11.14 | 11.16 | ||
Power supply | 380V 3N~ 50Hz | |||||
Internal machine | External static pressure | Pa | 100 | 200 | 270 | |
Noise | dB(A) | 58 | 61 | 62 | ||
Condensate pipe specifications | mm | DN25 | ||||
weight | kg | 180 | ||||
Dimensions | Long | mm | 1120 | |||
Wide | mm | 900 | ||||
High | mm | 713 | ||||
External unit | quantity | stage | 1 | |||
Noise | dB(A) | 41.5 | ||||
Refrigerant | Working quality | R410A | ||||
Charging volume | kg | 2.7 | ||||
Waterside heat exchangers | Take over the specifications | mm | 2xDN40 | |||
Circulating water flow | m³/hr | 5.144 | ||||
Waterside resistance | kPa | 47 | ||||
Dimensions | Long | mm | 600 | |||
Wide | mm | 480 | ||||
High | mm | 625 | ||||
weight | mm | 112 | ||||
Internal and external unit connection pipes | Liquid tubes | mm | F12.7 | |||
Steam pipes | mm | F19.05 | ||||